Unit of Measure

Gross Cooling Capacity

N/A 59000 Btu/hr

System Performance EER

N/A 11.6 19.9

System Performance SEER

N/A 15

AHRI Rated CFM

N/A 1375 ft³/min1800 ft³/min

AHRI Net Cooling Capacity

N/A 49000 Btu/hr57000 Btu/hr

Net Sensible Capacity

N/A 34800 Btu/hr40800 Btu/hr

Net Latent Capacity

N/A 14200 Btu/hr16200 Btu/hr

Net System Power

N/A 2.1 kW4.8 kW

Outdoor Sound Rating

N/A 83 dB

Refrigerant Charge

N/A 63 oz

Weight

N/A 576 lb

Shipping Weight

N/A 576 lb

Type

N/A Single-Stage Scroll

Fin Type

N/A Louvered

Tube Type

N/A MicroChannel

MicroChannel Depth

N/A 0.7 in

Face Area

N/A 16.4 ft²

Rows

N/A 1

FPI

N/A 23

Fin Type

N/A Louvered

Tube Type

N/A MicroChannel

MicroChannel Depth

N/A 1.3 in

Face Area

N/A 4.8 ft²

Rows

N/A 1

FPI

N/A 20

Refrigerant Control

N/A TX Valves

Drain Connection No.

N/A 1

Drain Connection Size

N/A 0.75 in

Type

N/A Propeller

No. Used

N/A 1

Diameter

N/A 24 in

Drive Type

N/A Direct

No. Speeds

N/A 1

CFM

N/A 3930 ft³/min

No. Motors

N/A 1

Horsepower

N/A 1/3 hp

Motor RPM

N/A 1075

Type

N/A FC Centrifugal

No. Used

N/A 1

Diameter

N/A 11 x 10 in

Drive Type

N/A Direct

No. Speeds

N/A Multiple

No. Motors

N/A 1

Horsepower

N/A 1 hp

Motor RPM

N/A 1050

Motor Frame Size

N/A 48 in

No. Filters

N/A 2

Recommended Size

N/A 1 x 16 x 25 in

Depth

N/A 48 1/16 in

Width

N/A 76 1/4 in

Height

N/A 35 in

N/A

  • R-410A HFC refrigerant.
  • Complete factory charged, wired and run tested.
  • Scroll compressors with internal line break overload and high-pressure protection.
  • Single stage compressor on all models. (except RLQN-C060 which utilizes 2 stage Ultra tech)
  • Convertible airflow.
  • TXV refrigerant metering system on each circuit.
  • High Pressure and Low Pressure/Loss of charge protection standard on all models.
  • Solid Core liquid line filter drier on each circuit.
  • Single slab, Micro Channel designed evaporator coil facilitates easy cleaning for maintained high efficiencies.
  • Cooling operation up to 125 degree F ambient.
  • Hinge door available as a factory installed option.
  • Easily removable filter, blower, electric heat, and control access panels permits prompt service.
  • Paint Finish meets ASTMB117 for maximum protection. G90 galvanized steel.
  • One piece top cover and one piece base pan with drawn supply and return opening for superior water management.
  • Externally mounted refrigerant gauge ports for easy service diagnostics.
  • Factory or field-installed electric heat kits available up to 24 kW.
  • Easy to install plug-in; slip in, 100% fully modulating economizer.
  • Forkable base rails for easy handling and lifting.
  • Single point electrical connections.
  • High performance belt drive motor with variable pitch pulleys and quick adjust belt system.
  • Permanently lubricated evaporator, condenser motors.
  • Condenser motors are internally protected, totally enclosed with shaft down design.
  • 1 inch filter standard with slide out design.
  • Colored and labeled wiring.
  • Molded compressor plug.
  • Factory Installed ClearControl™, a Direct Digital Control (DDC) and sensors which can connect to LonWorks™ or BACnet® BAS systems for remote monitoring and control.
  • Micro Channel evaporator and condenser coils deliver superior performance with less refrigerant charge and less weight than conventional copper tube/aluminum fin coils. In addition the all aluminum construction has superior protection against formicary corrosion and aluminum tube rubbing potential. Its easier to clean and has a more robust surface.