  • The size ranges offered by Rheem® allow you to mix or match components to meet actual job requirements, thus eliminating the need to use oversized or undersized equipment. Equipment sized to meet the actual load will provide better operating economy, better humidity control, and longer equipment life.
  • With an air cooled system, you have no water or sewer connections to make, and no troublesome and costly water treatment problems.
  • Since the Remote Heat Pump unit is located outside the building, and the low profile air handling unit can be installed in the drop ceiling or in the conditioned space, you will not need a separate equipment room which takes up valuable building space.
  • Remote mounting of the already quiet heat pump unit keeps the compressor and condenser fan noise outside, and the vertical discharge fans carry the sound up and away from the surrounding area.
  • Because of the simple design of the Rheem Remote Heat Pump unit, installation is quick and simple, and very little maintenance is required.
  • Energy Efficiency Ratings (EER’s) to 11.0!
Unit of Measure

Voltage

N/A 208 V230 V

Frequency

N/A 60 Hz

Number of Phases

N/A 3

Nominal Capacity

N/A 90000 Btu7.5 TR

Total Capacity

N/A 85000 Btu/hr

Net Sensible Capacity

N/A 58200 Btu/hr

Net Latent Capacity

N/A 26800 Btu/hr

EER

N/A 11.0

IEER

N/A 12.2

Indoor CFM

N/A 2650 ft³/min

Compressor Type

N/A Z-Scroll

Number of Compressors

N/A 1

Compressor - Rated Load Amperes (RLA)

N/A 22.4 A

Compressor - Locked Rotor Amperes (LRA)

N/A 164 A

Number of Fans

N/A 1

Fan Motor - Full Load Amperes

N/A 5.3 A

Minimum Circuit Ampacity

N/A 39 A

Fuse or HACR Circuit Breaker - Minimum

N/A 50 A

Fuse or HACR Circuit Breaker - Maximum

N/A 60 A

Outdoor Coil - Face Area

N/A 34.50 ft²

Outdoor Coil - No. Rows

N/A 2

Outdoor Coil - CFM

N/A 5000 ft³/min

Refrigeration Per Circuit

N/A 350.6 oz9939 g

Weight

N/A 389 lb

Shipping Weight

N/A 439 lb

Depth

N/A 31 1/8 in

Width

N/A 42 11/16 in

Height

N/A 48 13/16 in

N/A

  • CABINET—All access panels can be opened or removed without affecting the structural strength of the unit. Stamped louvered panels offer 100% protection for the condenser coil.
  • EQUIPMENT GROUND— Lug for field connection of ground wire.
  • CONTACTOR—The contactor is an electrical switch which operates the compressor and outdoor fans. Its 24 volt coil is activated on a call for cooling or heating.
  • TRANSFORMER—75 VA step-down type, from Line to 24 volts with resetable circuit breaker.
  • CAPACITOR—Help provide starting torque necessary to boost the condenser fan motors to operating speed by directing their stored energy to the starter winding in step with the running winding.
  • DEMAND DEFROST CONTROL—Used when unit is in heating mode to defrost outdoor coil.
  • AUTO-RESET HIGH PRESSURE CONTROL, AND AUTO-RESET LOW PRESSURE CONTROL—To provide compressor protection under abnormally high head pressure conditions (outdoor fan failure, restriction, dirty coil, etc.) or abnormally low suction pressure conditions (restrictions, TEV failure, loss of charge, indoor blower failure, etc.) while eliminating nuisance tripping sometimes experienced with conventional control systems.
  • COIL—Constructed with copper tubes and aluminum fins mechanically bonded to tubes for maximum heat transfer capabilities. All coil assemblies are leak tested up to 550 PSIG (3792 kPa) internal pressure.
  • SERVICE ACCESS—Control box with separate line and control voltages, as well as compressor and other refrigerant controls are accessible through access panels. An electrical access cover may be opened or removed without affecting normal operation of the unit. Condenser fan motors are equipped with molded plugs for easy removal. Louver panels and end access panel can be removed for coil cleaning.
  • BASE PAN—Galvanized steel with weather-resistant baked enamel finish.
  • COMPRESSOR—The Scroll Compressor is hermetically sealed with internal high temperature protection, and durable insulation on motor windings. The entire compressor is mounted on rubber grommets to reduce vibration and noise.
  • TX VALVE—Used when unit is in heating mode and outdoor coil functions as evaporator.
  • CRANKCASE HEATER—Minimizes refrigerant migration to compressor sump.
  • SUCTION LINE ACCUMULATOR—To prevent liquid slugging of compressor.
  • REFRIGERANT CONNECTIONS—All field sweat joints are made external of the unit and are located close to the ground for a neat looking installation.
  • SERVICE VALVES—Standard on liquid line and vapor line.
  • REVERSING VALVE—Sized for maximum capacity and efficiency, 24V coil, energized in heating.