Rheem Logo Background

CAD/BIM

  • Nominal sizes: 3-5 Tons
  • Up to 16.1 SEER2 / 11.0 EER2 / 7.2 HSPF2
  • Two stages of cooling and heating
  • Coil Type: Full MicroChannel
  • Standard Advanced Unitary Controller
  • Refrigerant Type: R-454B with factory-installed sensor
Unit of Measure

Sound Level

N/A 78 dB

Refrigerant Charge

N/A 4394 g155 oz

Voltage

N/A 460 V

Frequency

N/A 60 Hz

Number of Phases

N/A 3

Minimum Overcurrent Protection Device Size

N/A See Spec Sheet

Maximum Overcurrent Protection Device Size

N/A See Spec Sheet

Minimum Circuit Ampacity

N/A 15 A

Drive

N/A Direct Drive

Weight

N/A 562 lb245 kg

Shipping Weight

N/A 600 lb262 kg

Nominal Cooling Capacity

N/A 48000 Btu/h14.07 kW4 TR

EER2

N/A 11.0

SEER2

N/A 16.1

Nominal CFM

N/A 1600 ft³/min755 L/s

AHRI Rated CFM

N/A 1565 ft³/min739 L/s

AHRI Net Cooling Capacity

N/A 45500 Btu/h13.34 kW

Net Sensible Capacity

N/A 36400 Btu/h10.56 kW

Net Latent Capacity

N/A 9100 Btu/h2.64 kW

Net System Power

N/A 4.1 kW

Heating Capacity at 47°F

N/A 45500 Btu/h13.34 kW

Heating System Power at 47°F

N/A 3.6 kW3.60 COP

Heating Capacity at 17°F

N/A 27800 Btu/h8.15 kW

Heating System Power at 17°F

N/A 4.07 kW2.0 COP

HSPF2

N/A 7.2

Compressor Type

N/A Single 2-Stage Scroll

Fin Type

N/A Louvered

Tube Type

N/A MicroChannel

MicroChannel Depth

N/A 1.26 in32.00 mm

Face Area

N/A 16.11 ft²1.5 m²

Rows

N/A 1

FPI

N/A 16

Refrigerant Control

N/A TX Valves

Fin Type

N/A Louvered

Tube Type

N/A MicroChannel

MicroChannel Depth

N/A 1.26 in32.0 mm

Face Area

N/A 7.47 ft²0.69 m²

Rows

N/A 1

FPI

N/A 20

Refrigerant Control

N/A TX Valves

Drain Connection No.

N/A 1

Drain Connection Size

N/A 0.75 in19.05 mm

Type

N/A Propeller

No. Used

N/A 1

Diameter

N/A 26 in660.4 mm

Drive Type

N/A Direct

No. Speeds

N/A 1

CFM

N/A 1920 ft³/min9061 L/s

No. Motors

N/A 1

Horsepower

N/A 1/2 hp

Motor RPM

N/A 1200

Type

N/A FC Centrifugal

No. Used

N/A 1

Diameter

N/A 11 in279 mm

Drive Type

N/A Direct

No. Speeds

N/A Multiple

No. Motors

N/A 1

Horsepower

N/A 1 hp

Motor RPM

N/A 1400

Motor Frame Size

N/A 48

Type

N/A Disposable

Furnished

N/A Yes

No. Filters

N/A 4

Recommended Size

N/A 2x16x16 in51x406x406 mm

Depth

N/A 46 3/4 in

Width

N/A 79 1/4 in

Height

N/A 41 3/8 in

N/A Renaissance products are designed with a flexible footprint, thoughtfully engineered for easy, direct replacement of most other manufacturer's products without a roofcurb adapter. These units also boast industry-leading serviceability features through the standard ServiceSmart package as well as a new advanced unitary controller that arrives with factory pre-configured control sequences to reduce set-up and commissioning time and is BACnet® MS/TP and IP native for seamless integration with building automation systems (BAS). Units exceed ASHRAE 90.1 energy efficiency levels and deliver powerful cooling operation up to 125°F.

Standout Features:

  • Advanced unitary controller for faster setup, commissioning and troubleshooting
  • Patented flex-fit filter rack, qwik-slide blower assembly and qwik-clean drain pain for quick, easy service and maintenance
  • PlusOne® SmartShield™ with patented microchannel defrost system
  • Field convertible airflow (downflow and horizontal)
  • Universal 24V & BACnet® MS/TP- and BACnet IP-ready
Available power options:
  • 208-230V / 1 phase / 60 Hz
  • 208-230V / 3 phase / 60 Hz
  • 460V / 3 phase / 60 Hz
Limited Warranty (Commercial Applications): Parts – 1 Year, Compressor – 5 Years. Additional extended warranty packages available through ProtectionPlus®. All units are factory run tested and shipped with R-454B refrigerant charge.