Sound Level |
N/A 89.2 dB |
Refrigerant Charge |
N/A 6066.8 g214 oz |
Voltage |
N/A 460 V |
Frequency |
N/A 60 Hz |
Number of Phases |
N/A 3 |
Minimum Circuit Ampacity |
N/A 26 A |
Minimum Overcurrent Protection Device Size |
N/A See Spec Sheet |
Maximum Overcurrent Protection Device Size |
N/A See Spec Sheet |
Weight |
N/A 1009 lb458 kg |
Shipping Weight |
N/A 1048 lb475 kg |
EER |
N/A 12 |
IEER |
N/A 17.6 |
Nominal Cooling Capacity |
N/A 90000 Btu/h26.37 kW |
Nominal CFM |
N/A 2800 ft³/min1321 L/s |
AHRI Rated CFM |
N/A 2550 ft³/min1203 L/s |
AHRI Net Cooling Capacity |
N/A 86000 Btu/h25.2 kW |
Net Sensible Cooling Capacity |
N/A 68800 Btu/h19.95 kW |
Net Latent Cooling Capacity |
N/A 17200 Btu/h4.99 kW |
Net System Power |
N/A 7.2 kW |
Heating Capacity at 47°F |
N/A 86000 Btu/h25.2 kW |
Heating System Power at 47°F |
N/A 7.00 kW3.60 COP |
Heating Capacity at 17°F |
N/A 55000 Btu/h16.12 kW |
Heating System Power at 17°F |
N/A 6.45 kW2.50 COP |
Fin Type |
N/A Louvered |
Tube Type |
N/A MicroChannel |
MicroChannel Depth |
N/A 1.26 in32.00 mm |
Face Area |
N/A 28.8 ft²2.68 m² |
Rows |
N/A 1 |
FPI |
N/A 16 |
Fin Type |
N/A Louvered |
Tube Type |
N/A MicroChannel |
MicroChannel Depth |
N/A 1.26 in32.0 mm |
Face Area |
N/A 13.2 ft²1.23 m² |
Rows |
N/A 1 |
FPI |
N/A 20 |
Refrigerant Control |
N/A TX Valves |
Drain Connection No. |
N/A 1 |
Drain Connection Size |
N/A 0.75 in19.05 mm |
Type |
N/A Propeller |
No. Used |
N/A 2 |
Diameter |
N/A 24 in609.6 mm |
Drive Type |
N/A Direct |
No. Speeds |
N/A 1 |
CFM |
N/A 8000 ft³/min3775 L/s |
No. Motors |
N/A 2 |
Horsepower |
N/A 1/2 hp |
Motor RPM |
N/A 1200 |
Type |
N/A BC Centrifugal |
No. Used |
N/A 1 |
Diameter |
N/A 23.03 x 11.10 in585 x 282 mm |
Drive Type |
N/A Direct |
No. Speeds |
N/A Multiple |
No. Motors |
N/A 1 |
Horsepower |
N/A 5 hp |
Motor RPM |
N/A 2000 |
Motor Frame Size |
N/A 150 |
Type |
N/A Disposable |
Furnished |
N/A Yes |
No. Filters |
N/A 4 |
Recommended Size |
N/A 2 x 20 x 20 in51 x 508 x 508 mm |
|
N/A
Renaissance products are designed with a flexible footprint, thoughtfully engineered for easy, direct replacement of most other manufacturer's products without a roofcurb adapter. These units also boast industry-leading serviceability features through the standard ServiceSmart package as well as a new advanced unitary controller that arrives with factory pre-configured control sequences to reduce set-up and commissioning time and is BACnet® MS/TP and IP native for seamless integration with building automation systems (BAS). Higher efficiency performance is delivered through innovative technologies such as the backward-curve direct-drive indoor blower, full MicroChannel coils, and tandem compressors with multiple stages of operation. Units exceed ASHRAE 90.1 energy efficiency levels and deliver powerful cooling operation up to 125°F.
|